| Download link | Main Page | Reports |
CRITICAL
BUILDING
CHARACTERISTICS
“ . . . the most important decisions that affect. . . .
getting a decent building, occur in the very preliminary phases of design. . .
. it's a little like almost anything else ‑ if you start off on the right
path, it's not hard to do things right. . . ."
– Henry Degenkolb, Structural Engineer
So far, we have been
describing the input motion – the characteristics of ground motion that
affect the building. However, there
also are some important things about a building itself that, in conjunction
with the ground motion, affect its performance and may dictate whether it
collapses or survives.
PERIOD AND AMPLIFICATION
Another very important
characteristic of earthquake waves is their period or frequency – that is,
whether the waves are quick and abrupt or slow and rolling. This phenomenon is particularly important
for determining building seismic forces.
|
|
All objects have a natural
or fundamental period; this is the rate at which they will move back and
forth if they are given a horizontal push.
In fact, without dragging it back and forth, it is not possible to make
an object vibrate at anything other than its natural period. When a child in a swing is started with a
push, to be effective this shove must be as close as possible to the natural
period of the swing. If correctly
gauged, a very small push will set the swing going nicely. Similarly, when earthquake motion starts a
building vibrating, it will tend to sway back and forth at its natural period.
When a vibrating
structure is given further pushes that are also at its natural period, the
structure tends to resonate. Its
vibrations increase dramatically in response to even rather small pushes and,
in fact, its accelerations may increase as much as four or five times.
Natural periods vary
from about 0.05 seconds for a piece of equipment such as a filing
cabinet to about 0.1 seconds for a one-story building. Period is the inverse of frequency so the
cabinet will
|
|
vibrate at 1/0.05 = 20
cycles a second or 20 Hertz. A
four-story building will sway at about a 0.5 second period and
taller buildings between about 10 and 20 stories will swing at periods of about
1 to 2 seconds. A rule of
thumb is that the building period equals the number of stories divided by 10;
therefore, period is primarily a function of building height. The 60-story Citicorp building in New York
has a period of 7 seconds; give it a push and it will sway slowly back
and forth completing a cycle every 7 seconds.
Other factors such as the building's construction materials, which
affect the stiffness of the structure, and the building's geometric proportions
also affect the period, but height is the most important consideration.
Taller buildings also
will undergo several modes of vibration so that the building will
wiggle back and forth like a snake. For
seismic purposes, however, the natural period generally is the most
significant.
The ground, of course,
also vibrates at its natural period.
The natural period of ground in the United States varies from about 0.4
seconds to 2 seconds depending generally on the hardness
of the ground. Very soft ground may
have a period of up to 2 seconds since it cannot sustain longer
period motions except under certain unusual conditions. Since this range is well within the range of
common building periods, it is quite possible that the pushes that the ground
gives the building will be at the natural period of the building. This may create resonance, causing
the structure to have to deal with accelerations of perhaps 1 "g"
when the ground is only vibrating with accelerations of 0.2 "g."
|
|
The terrible
destruction in Mexico City in the earthquake of 1985 was primarily the result
of response amplification caused by coincidence of building and ground motion
periods. Mexico City was some 250 miles
from the earthquake focus, and the earthquake caused the soft ground under the
downtown buildings to vibrate for over 90 seconds at its long natural period of
around 2 seconds. This caused tall
buildings between about 10 and 20 stories to resonate at a similar period,
greatly increasing the accelerations within them. This amplification in building vibration is very undesirable. The possibility of it happening can be
reduced by trying to ensure that the building period will not coincide with
that of the ground. Thus, on soft (long
period) ground, it would be best to design a short stiff (short period)
building.
There is also a more
general amplification effect related to different types of ground. Earthquake ground shaking tends to be
greater on soft ground than on hard ground such as rock. As a result, earthquake damage tends to be
more severe in areas of soft ground.
This characteristic became very clear when the 1906 San Francisco earthquake
was studied and maps were drawn that showed building damage in relation to the
ground conditions. Studies after the
1989 Loma Prieta earthquake also showed that shaking in the soft ground around
San Francisco Bay was two and a half to three and a half times that of shaking
in rock. Extensive damage was caused to
buildings in San Francisco's Marina district, which was largely built on filled
ground, some of it rubble deposited after the 1906 earthquake.
|
|
To assist the engineer
in determining whether there may be a problem because the period of a new
building is close to that of the site, curves for the site can be drawn (based
on information about the nature of the ground) that show estimates of the
periods at which maximum building response is likely – that is, the
building periods for which maximum shaking can be anticipated. Such a curve is termed the site response
spectrum. This spectrum shows the
accelerations (on the vertical ordinate) that may be
expected at varying periods (the horizontal ordinate). Thus, the response spectrum illustrated
shows a maximum response at a period of about 0.3 seconds – the fundamental
period of a mid‑rise building.
Based on this knowledge, the building design might be adjusted to ensure
that the building period does not coincide with the site period of maximum
response. For the figure shown, with a
maximum response at about 0.3 seconds, it would be appropriate to design a
building with a longer period of 1 second or more. Of course, it is not always possible to do this, but the response
spectrum shows clearly what the possible accelerations at different periods are
likely to be and the building can then be designed accordingly.
DAMPING
The important
relationship between the building and ground motion periods was illustrated in
Chapter 3 using a the child's swing to show how the swinging motion is
amplified by an input motion, in this case a judicious push. However, the child’s swing is a pendulum
that vibrates very efficiently and continue to swing for many minutes after any
assistance even though the amplitude will diminish. Buildings and other objects do not swing as efficiently as
pendulums because the vibration is damped or reduced. The extent of damping in a building depends
on the materials of construction, how those materials are connected together,
and on its architectural elements such as partitions, ceilings, and exterior
walls.
HIGHER FORCES AND UNCALCULATED
RESISTANCE
Even if a building is
well damped and will not resonate, it may be subjected to forces that are much
higher than the computed forces for which it was designed. Why is this the case? Because designing a building for the rare
maximum conceivable earthquake forces and then adding a factor of safety of
two or three times as is done for vertical loads would result in a very
expensive structure whose functional use would be impeded by huge walls and
columns.
Experience shows,
however, that many buildings have encountered forces far higher than they were
designed to resist and yet have survived, sometimes with little damage. This phenomenon can be explained by the fact
that the analysis of forces is not precise and deliberately errs on the
conservative side so that the building can really survive higher forces than is
apparent. In addition, the building
often gains additional strength from components, such as partitions, that are
not considered in an analysis. Some
structural members may be sized for adequate stiffness rather than for
strength. Finally, materials often are
stronger in reality than the engineer assumes in his calculations. Taken together, these factors provide a
considerable safety factor or uncalculated additional resistance.
DUCTILITY
|
|
An additional property
of materials is used to ensure that a building may adequately resist much more
than its design ground shaking. This
material property is called ductility.
Ductility is the characteristic of certain materials – steel in
particular – to fail only after considerable distortion or deformation has
occurred. This is why it is much more
difficult to break a metal spoon by bending it than one made of plastic. The metal object will remain intact – though
distorted – after successive bending to and fro while the plastic spoon will
snap suddenly after a few bends. The
metal is far more ductile than the plastic.
The deformation of the
metal (even in the spoon) absorbs energy and defers absolute failure of the
structure. The material bends but does
not break and so continues to resist forces and support loads, although with
diminished effectiveness. The
effect of earthquake motion on a building is rather like that of bending a
spoon rapidly back and forth – the heavy structure is pushed back and forth in
a similar way several times a second (depending on its period of vibration).
Brittle
materials, such as unreinforced brickwork or unreinforced concrete, fail
suddenly with a minimum of distortion.
However, the steel contained in a well designed modern reinforced
concrete structure can give the combined material the ductility that is needed
for earthquake resistance.
Thus, buildings are
designed in such a way that in the rare case when they are subjected to forces
higher than those required by a code, the materials and connections will
distort but not break. In so doing,
they will safely absorb the energy of the earthquake vibrations, and the
building, although distorted and possibly unusable, is at least still standing.
OVERTURNING
Although building mass
or weight was discussed as part of the F = MA equation for
determining the horizontal forces, there is another way in which the building's
weight may act under earthquake forces to overload the building and cause
damage or even collapse.
|
|
Vertical members such
as columns or walls may fail by buckling when the mass of the building
exerts its gravity force on a member distorted or moved out of plumb by the
lateral forces. This phenomenon is
known by engineers as the P‑e or P‑delta effect,
where P is the gravity force or weight and e or delta is the eccentricity
or the extent to which the force is offset.
All objects that overturn do so as a result of this phenomenon.
The geometrical
proportions of the building also may have a great influence on whether the P‑delta
effect will pose a problem since a tall slender building is much more likely to
be subject to overturning forces than a low squat one. However, in earthquakes, buildings seldom
overturn. This is because structures
are not homogeneous but are composed of many elements connected together; the
earthquake forces will pull the components apart and the building will fall down,
not over. Strong, homogeneous
structures such as filing cabinets, however, will fall over.
|
|
|
|
STRENGTH, STIFFNESS, AND DRIFT
|
|
Two important related
characteristics of any structure are its strength and its stiffness. Two structural beams may be equally strong
(or safe) in supporting a load but may vary in their stiffness – the extent to
which they bend or deflect in doing so.
Stiffness is a material property but it also is dependent on shape. This concept can be easily understood by
visualizing the flexibility of a long ruler placed where it has to support a
load; how well it supports the load will depend on whether the load is placed
on the ruler's flat surface or on its edge.
|
|
The measure of
stiffness is deflection, the extent to which a structural element moves
or bends when loaded. For vertical
gravity loads, this is usually the only aspect of stiffness that is of
concern. When floor joists are designed
for a house, for example, it is often deflection rather than strength that
dictates the size of the joists – that is, the depth of the joists is
determined by how much they will bend under load rather than by whether they
can safely support the floor loads.
Typically, an unacceptable amount of bending will occur well before the
joists are stressed to the point at which they may break because of the
loads. (Stress refers to the internal
forces within a material or member. The
stress is created as the structural member resists the applied load. Stress is expressed in force per unit area –
for example, pounds per square inch.
Codes provide stress limits that are not to be exceeded for commonly
used materials.)
The analogous lateral
force condition occurs when limitations on drift, the horizontal story‑to‑story
deflection, impose more severe requirements on members than the strength
requirements. Drift limits serve to
prevent possible damage to interior or exterior walls that are attached to the
structure and which might be cracked or distorted if the structure deflects too
much laterally. The strength issue
involves using a material strong enough to resist a load without exceeding a
safe stress in the material while the drift issue involves preventing a structure
from moving out of vertical alignment more than a given amount.
|
|
In seismic design,
there is another very important aspect to stiffness. The problem of determining the overall lateral force on the
building by multiplying the building weight by its acceleration has already
been discussed. But how is this force
distributed among the various elements of a building? The engineer needs to know this so that each member and
connection can be properly designed to withstand the forces it may encounter. Relative stiffness enters into this
issue because the applied forces are "attracted to" and concentrated
at the stiffer elements of the building – in engineering terms, the forces are distributed
in proportion to the stiffness of the resisting elements.
Why this is so can be
understood by visualizing a heavy block supported away from a wall by two short
beams. Clearly, the thick, stiff beam
will carry much more load than the slender one, and the same is true if they
are turned 90 degrees to simulate the lateral force situation.
|
|
An important aspect of
this for column lateral stiffness is illustrated in the next sketch. Mathematically, the stiffness of a column
approximately varies as the cube of its length. In this diagram, the columns have the same cross‑section
but the short column is half the length of the long one. Therefore, the short column will be eight
times stiffer (23) instead of twice as stiff and will take eight
times the horizontal load of the long column. This concept has serious implications for buildings with columns
of different lengths, and in designing a building, the engineer tries to
equalize the stiffness of the resisting elements so that no one member or small
group of members takes a disproportionate amount of the load. If this cannot be done (for architectural
reasons, for example), then the designer must make sure that stiffer members
are appropriately designed to carry their proportion of the load.
CONFIGURATION: SIZE AND SHAPE
The size, shape, and
geometrical proportions of a building are termed its configuration. How the building configuration relates to
its structural systems has a major influence on the building's ability to
withstand shaking.
Many years ago when
engineers first started studying the earthquake problem in a systematic way,
they noticed that buildings with certain shapes and proportions seemed to be
more prone to damage in earthquakes than others no matter what construction
materials or structural systems had been used.
In general, the more irregular the building – that is, the more
the building deviated from a regular simple symmetrical shape – the more likely
it seemed to suffer damage.
In the past, buildings
tended to have simple configurations because traditional materials such as
stone and brick did not allow for much more than superficial or surface
decorative irregularity in design. (Sometimes, as in a medieval Gothic
cathedral or a Renaissance Italian palace, this surface
"irregularity" achieved the highest and most enduring form of art.) But starting in the late nineteenth
century, modern steel and reinforced concrete frame construction allowed for
increased structural daring and permitted architects to conceive designs that
would have been impossible with traditional masonry. Configuration irregularity results in two main effects – stress
concentrations and torsional forces.
|
|
|
|
|
|
Stress
Concentrations
Irregularities tend to
create abrupt changes in strength or stiffness that may concentrate forces in
an undesirable way. These can be very
difficult to deal with even in a modern structure. So, although the size of the overall force that the building must
withstand is determined by the F = MA equation, the way in which
this is distributed and concentrated is determined by the configuration.
|
|
|
|
Stress
concentration means that an undue proportion of the overall
forces is concentrated at one or a few points of the building such as a
particular set of beams, columns, or walls.
These few members may fail and, by a chain reaction, bring down the
whole building. Because, as has been
noted, forces are attracted to the stiffer elements of the building, these also
tend to be locations of stress concentration.
People who are in the building demolition business know that if they weaken
a few key columns or connections in a building, they can bring it down. An earthquake also tends to "find"
these "weak links."
Stress concentration
can also be created by vertical irregularity.
The most serious condition of vertical irregularity is that of the soft,
or weak, story in which one story, usually the first, is significantly weaker
or more flexible than those above. A
high first story is often architecturally desirable to accommodate larger rooms
– lobbies, banking floors, or hotel meeting rooms. The design creates a major stress concentration at the points of
discontinuity and, in extreme circumstance, may lead to collapse unless
adequate design is provided at such points.
A common example of the soft first story occurs in apartment houses,
which often allocate all or most of the first floor to parking, with widely
spaced columns and a minimum of walls.
The first floor of the Northridge Meadows apartments, designed before
the problem of the soft first story was fully understood, collapsed in the 1994
Northridge earthquake, with considerable loss of life. Many other similar apartments also collapsed
or were severely damaged, but fortunately only automobiles were destroyed.
|
|
|
|
Torsional
Forces
In addition to stress
concentrations, irregularities, particularly in plan, may permit what are
called torsional or twisting forces to develop, which contributes a
significant element of uncertainty to an analysis of building resistance. ("Plan" refers to the horizontal
layout of the building which may be a simple square or rectangular or an
irregular shape with wings of different shapes and proportions.)
Torsional forces are
created in a building by a lack of balance between the location of the
resisting elements and the arrangement of the building mass. Engineers refer to this as eccentricity
between the center of mass and the center of resistance, which
tends to make the building rotate around the latter and creates torsion in the
resisting elements. In a building, the
main lateral force is contributed by the weight of the floors, walls, and roof,
and this force is exerted through the center of mass, usually the geometric
center of the floor (in plan). If the
resistance provided by walls and columns pushes back through this point (the
center of resistance), then there is no torsion and balance is maintained. If not, torsion is introduced and dangerous
concentrations of stress can be created.
This is the reason why it is recommended that buildings in areas of
seismic risk be designed to be as symmetrical as possible.
One building
configuration that is most likely to produce torsion features re-entrant
corners (buildings shaped like an L or a T for example). The wings of such buildings tend to twist
and produce torsional forces. In addition,
re-entrant corner buildings also tend to produce stress concentration
at the "notch" where the wings meet because this location often is
stiffer and therefore attracts a higher proportion of the forces.
Buildings that have
large variations in their perimeter resistance on different sides
of the building also tend to produce torsion.
This form of variation in perimeter resistance occurs often in
buildings such as stores in which side and end walls may be masonry or concrete
party walls while the front wall may be largely glass. The centers of mass and resistance do not
balance and, in extreme cases, the building can tear itself apart.
|
|
|
|
|
|
NONSTRUCTURAL COMPONENTS
For a long time,
seismic building codes focused exclusively on the structure of the
building – that is, the system of columns, beams, walls and diaphragms that
provides resistance against earthquake forces.
Although this focus remains dominant for obvious reasons, experience in
more recent earthquakes has shown that damage to nonstructural components
is also of great concern. In most
modern buildings, the nonstructural components account for 60 to 80 percent of
the value of the building.
|
|
Nonstructural
components surround us at work or at home – ceilings, partitions, light
fixtures, windows, and exterior walls.
They are also the components that enable the building to function -‑
the power, heating, cooling, and elevator systems and, for buildings like
hospitals, the medical equipment that maintains or saves lives. Damage to nonstructural components can
result in great economic loss, in terms of both the cost of repair and the loss
of building use and business interruption while the building is closed for
repair. If the building is a critical
facility such as a hospital, damage to utility systems providing such things as
water and power may shut the building down when it is most needed.
Nonstructural damage
often is caused by movement of the building structure that is perfectly
acceptable as far as the safety and stability of the structure is
concerned. But the nonstructural
components and finishes that are rigidly attached to the structure are bent and
twisted in way that they cannot
accommodate with the result that tiles fall off walls and plaster partitions
and ceilings crack. This kind of damage
is hazardous to occupants and can be difficult and expensive to repair.
CONSTRUCTION QUALITY
One other
characteristic that applies to any building must be mentioned: it must be constructed well if it is to
perform well. The materials from which
it is constructed must have the necessary basic strength and expected
properties. Most important, all the
building's components must be securely connected together so that as they push
and pull against one another during the earthquake, the connections are strong
enough to transfer the earthquake forces and thereby maintain the integrity of
the structure.
FRAMING SYSTEMS
How does an engineer
design a building to resist all the forces that are produced by ground
motion? Essentially, he must choose
from a small set of components and then combine them in his design to form a
complete resistance system.
|
|
Three kinds of framing
systems can resist the lateral forces generated in a building by an earthquake
– shear walls, braced frames, and moment resisting frames
(sometimes called rigid frames). These
three types of framing system are really alternatives. Although designers sometimes mix components,
using one type in one direction and another type in the other, this is
inadvisable, mainly because the different systems have different stiffnesses
and it is difficult to obtain balanced resistance when they are mixed.
Thus, the designer
generally chooses only one type of framing system to resist the applied
loads. This must be done at an early stage
in the design because the different characteristics of these components have a
considerable effect on the architectural design, both functionally and
aesthetically. For example, if shear
walls are chosen as the seismic force resisting system, the building
will feature a pattern of permanent structural walls that run through every
floor from roof to foundation. While
this may be acceptable if the building is to be an apartment house or hotel, it
will not work well if the building is to be a rental office building where
internal space requirements will change regularly.
|
|
It should be noted
that moment resistant frames sometimes are combined with one of the other
systems to produce a dual system, in which the moment resistant frame
backs up the other system. In this
case, the two systems interact to share the load.
In the horizontal
plane, diaphragms, generally formed by the floor and roof elements of
the building, are necessary.
(Sometimes, however, horizontal bracing systems independent of the roof
or floor structure serve as diaphragms.)
Diaphragms transfer the lateral forces to the vertical resistant
elements – the shear walls or frames.
|
|
Shear
walls are designed to receive lateral forces from diaphragms and transmit
them to the ground. The forces in these
walls are predominantly shear forces in which the material fibers within the
wall try to slide past one another. A
card house is a shear wall structure, and sufficient "card" walls
must be placed at right angles to one another or the house will collapse. It is a very inefficient structure because
the connections between the walls and between the walls and the diaphragms are
nonexistent. If the walls are connected
by slots or by tape, the structure is transformed into one that is very efficient
for its size and weight. Similarly, the
connections between the walls and floor and roof diaphragms in a building must
be very strong and ductile.
|
|
|
|
Braced
frames act in the same way as shear walls; however, they generally provide
less resistance but better ductility depending on their detailed design. Bracing provides lateral resistance through
triangulated geometry, which prevents the frame from folding up if given a
sideways push. A bicycle is a familiar
example of a braced frame; without the connecting diagonal brace, the other
members and connections would have to be much stronger to prevent the frame
from folding up.
In a building with a
braced frame, lateral forces may cause the bracing to successively elongate and
compress causing it to lose its effectiveness and experience large distortions
that ultimately lead to collapse of the vertical structure it is trying to
brace. Ductility therefore must be
designed into the bracing so that it will deform but not snap.
|
|
A moment resistant
frame is the engineering term for a frame structure in which the lateral
forces are resisted primarily by bending in the beams and columns that is
mobilized by strong rigid joints between columns and beams. (To engineers, a "moment" of a
force about a point is the force multiplied by the distance between the point
and the line of action of the force.)
A simple ladder is an example of a moment resistant frame. In a building that uses a moment resistant
frame, no walls or braced frames are required.
The joints, however, become highly stressed and the details of their
construction are very important in both steel and reinforced concrete.
As a last resort,
moment resistant frames use the energy absorption obtained by ductility – that
is, the permanent deformation of the structure prior to ultimate failure. For this reason, moment resistant frames
generally are steel structures with bolted or welded joints in which the
natural ductility of the material is an advantage. However, properly reinforced concrete frames that contain a large
amount of precisely located steel reinforcing also are effective as ductile
moment frames.
| Main Page | UP | Reports |